* Application HYR 2-815 Series Regulator is designed for to use commercial place such as restaurant business, hotel, school, public building or factory etc to supply natural gas. It is suit for boiler or burning equipment device, small & medium device regulator. * Character It is easy to install (verticality and horizontality connecting pipe, Case rotate attachment) Can choice proper orifice according to first stage pressure and capacity. Orifice, Seat disc etc replacement and maintain is possible without disconnecting regulator body to pipe. * Specifications Inlet Pressure range 0.015~0.99 MPa Outlet Pressure range 1.6~45.0kPa(160~4500mmH2O) Relief valve Setting Pressure 3.2~67.0kPa(320~6700mmH2O) OPSO Setting Pressure 3.0~70.0kPa(300~7000mmH2O) Max. capacity Refer to detailed specification Connection Size 50A-10K flange(Rf type) Model Type HYR 2-815 built-in relief valve, OPSO HYR 2-815 OPSO With OPSO * Capacity Table HYR 2-815 Series Capacity table is indicating inlet pressure changing and capacity fluctuation according to orifice size. Standard object is natural gas. (gravity=0.6, standard state N ㎥/hr) * HYR 2-815 OPSO Regulator Construction * SPRING Adjusting Spring Spring No. Pressure Range Color Ms 2815 1.6~2.6kPa Green Ms 2815-15 10~18kPa White Ms 2815-25 16~30kPa Biue Ms 2815-40 28~45kPa Yello OPSO Spring Spring No. Pressure Range Color Os 81 3.0~4.8kPa Green Os 81-15 20~27kPa White Os 81-25 33~45kPa Biue Os 81-40 52~70kPa Yello Relief valve Spring Spring No. Pressure Range Color Rs 215 P2+1.2~2.8kPa Green Rs 215-15 P2+4.0~9.0kPa White Rs 215-25 P2+10.0~15.0kPa Biue Rs 215-40 P2+12.0~27.0kPa Yello Unit : mmH20 * Regulator abnormality cause and settlement 1) Outlet part second pressure is drop 1) Cause Orifice size is small against to using capacity Gas supply is interrupted due to block gas filter Diaphragm is expanded due to long time using OPSO is locked up 2) Settlement Replace suitable orifice according to using capacity Disassembly gas filter and cleaning inside Disassembly case and replace diaphragm Block inlet & outlet valve and release gas. And then, restore OPSO. 2) Outlet part second pressure is increasing 1) Cause Lock-up condition is bad due to valve seat or orifice wear, crack etc First stage inlet pressure is applied toward OPSO because of OPSO Shaft O-ring damage Assembly lever linked diaphragm operation is not good Volume changing is happen due to temperature First stage inlet pressure is applied due to orifice sealing condition 2) Settlement Disconnecting case from pipe and replace valve seat and orifice Disconnecting OPSO from pipe and replace shaft O-ring Disassembly case and replace Assembly lever Keeping warm the expose pipe Re-assembly orifice sealing by sealing materials 3) In case of regulator hunting 1) Cause Orifice size is too much big against to capacity and pressure First stage pressure is unstabilized Inflow contamination materials or humidity to inside of second stage pipe Happening spring and diaphragm deformation due to long time use Large volume of gas is instantaneously & repeatedly flow and cut off. 2) Settlement Replace suitable orifice according to using capacity and pressure Disassembly and inspect filter Remove inside of contamination materials and humidity Disassembly case and inspect and then replace spring and diaphragm Secure sufficient second stage pipe volume
|